Electrical designated persons, safe work and periodic inspections
Central · Requirement · Version 1
Checked extractOfficial source available
Applicability
Scoped Regulations 3–4, 21 and 32 from the 2023 text; notified voltage and actual inspection period depend on the Appropriate Government. Not represented as a complete consolidated installation approval.
Competent person
A designated electrical worker needs an Appropriate Government competency certificate or electrical work permit and entry in the designated-person register.
Only designated persons observing the relevant Schedule I precautions may operate/maintain electrical plant or assist. Supply suitable protective equipment and devices, maintain them soundly, and earth non-current-carrying switchgear/control-panel parts with appropriate insulating floor/mat.
Above notified voltage: Electrical Inspector inspection. At/below that voltage: self-certification, subject to specified exceptions. Appropriate Government sets periodicity, not exceeding five years; mines, oil-fields and railways have additional central/Inspector provisions.
Electrical installations, electrical plants and lines, and persons involved in electricity generation, transmission, distribution, trading, supply or use; see Regulation 1(3).
Original 2023 Gazette text, English pages numbered 100–183. CEA lists a 2026 amendment which is captured separately for visual review; original text is not represented as consolidated current regulations.