CEA earthing above 650 V: connections, annual tests and crossing-guard limit

Central · Requirement · Version 1

Checked extractOfficial source available

Applicability

Regulation 50 concerns apparatus exceeding 650 V. Its common-grid permission is conditional on voltage exceeding 33 kV and system design. The 25-ohm limit applies only to the specified overhead crossing guards, not all factory earthing. Supplier and consumer annual-test duties are separate from the supplier-only Regulation 43 duties.

Earthing-system or mat performance

Earthing-system or mat performance
ProvisionApplicable casePrescribed requirement
50(1)(i)Entire switchyard/substation equipment and buildings, including associated non-current-carrying metal partsEffectively earth to a system or mat that limits touch and step potential to relevant-standard tolerable values.
50(1)(ii)The same earthing system or matLimit earth-potential rise to relevant-standard tolerable values, preventing danger from transferred potential through ground, earth wires, cable sheath, fences, pipelines or similar equipment.
50(1)(iii)The same earthing system or matMaintain earth-connection resistance so the protective device operates effectively.

Neutral connections and conditional alternatives

Neutral connections and conditional alternatives
ProvisionApplicable casePrescribed requirement
50(2)(i)Star-connected system with earthed neutrals or delta-connected system with earthed artificial neutralEarth every generator/transformer neutral by not less than two separate and distinct connections.
50(2)(i), first provisoGenerator neutralMay connect to earth through impedance to limit fault current.
50(2)(i), second provisoMulti-machine systemMay resort to neutral switching to limit injurious harmonic-current circulation.
50(2)(ii)Appreciable harmonic current in neutral connection interfering with communication circuitsEarth generator or transformer neutral through suitable impedance.
50(2)(iii)Delta-connected systemObtain a neutral using an earthing transformer and current-limiting resistance or impedance wherever considered necessary at system commencement.
Source reference: CEA (Measures relating to Safety and Electric Supply) Regulations, 2023 — original text · p. 21; Regulation 50(2)(i)-(iii) and provisos

Common-grid permission above 33 kV

In generating stations, substations and other installations exceeding 33 kV, neutral and protective-frame earthing may be integrated into a common grid if system design warrants, provided combined-mat resistance does not cause step and touch potentials to exceed relevant-standard values.

Single-phase and concentric-line earth connections

Single-phase and concentric-line earth connections
ProvisionApplicable casePrescribed requirement
50(4)Single-phase systems exceeding 650 VEffectively earth the system.
50(5)Electric supply lines with concentric cablesConnect the external conductor with earth.

Annual supplier or consumer earth tests and records

Every supplier-owned or consumer-owned earthing system shall be resistance-tested on a dry day during the dry season not less than once in a year. Maintain records and produce them before the Electrical Inspector if required.

Source reference: CEA (Measures relating to Safety and Electric Supply) Regulations, 2023 — original text · p. 21; Regulation 50(8); p. 22; Regulation 50(8) record-production continuation

Restricted overhead crossing-guard condition

Where the earthing lead and connection are used only in connection with earthing guards under overhead lines exceeding 650 V but not exceeding 33 kV, crossing a telecommunication or railway line, and those lines have an earth-leakage protective device, earth resistance shall not exceed 25 ohms. Project authorities shall obtain no-objection certificates from Railway Authorities and the Power and Telecommunication Coordination Committee before energisation.

Crossing-guard maximum earth resistance (ohms)

25

Source reference: CEA (Measures relating to Safety and Electric Supply) Regulations, 2023 — original text · p. 21; Regulation 50(7): twenty five ohms under its specified conditions

Source document

Official sources & provenance

CEA (Measures relating to Safety and Electric Supply) Regulations, 2023 — original text

Central Electricity Authority, Ministry of Power

Published
12 Jun 2023
Effective from
12 Jun 2023
Verification
reviewed
Captured
01/10/2026
PDF SHA-256
2b1ee07ef090f2a0b2c2673e117fdff1e9821c54d5f7812fd77958e1dcf70add
View official source ↗View captured PDF ↗

Electrical installations, electrical plants and lines, and persons involved in electricity generation, transmission, distribution, trading, supply or use; see Regulation 1(3).

Original 2023 Gazette text, English pages numbered 100–183. CEA lists a 2026 amendment which is captured separately for visual review; original text is not represented as consolidated current regulations.

CEA electrical safety amendment, 2026 — battery storage rules commencing April 2027

Central Electricity Authority, Ministry of Power

Published
30 Mar 2026
Effective from
1 Apr 2027
Verification
reviewed
Captured
01/10/2026
PDF SHA-256
8314ccff23f429fd652e7ac92e9a46d7575cdcbc278d2ac6f0abd561778efeb1
View official source ↗View captured PDF ↗

Upcoming battery energy storage system provisions in Chapter XA. Regulations 122A–122M cover BESS above 650 V; Regulation 122N addresses BESS at or below 650 V. Commencement is 1 April 2027, not 2026.

Original scanned Gazette manually rendered and read on PDF pp. 1, 4–7. Publication header, English commencement clause and limited BESS scope reviewed. This amendment is upcoming as of 5 October 2026; current 2023 regulations remain separate. No OCR or complete technical compliance certification is claimed.

Back to library records